Network Catalog

 

MICON ORDERING DATA



All of the Dossert MICON connectors are furnished, unless otherwise specified, with #63 size outlets as standard connector units. There are also available outlet sizes #88 and #112 which permit use of larger cable sizes in the outlet positions. The following Table 1. shows the outlet size number, with the corresponding range of specific cable sizes and the receptacle stud mounting thread size.

TABLE 1.

Outlet  Size Number

Range of specific Cable Sizes Handled by Outlet

Stud Mounting Thread Size
  MIN MAX.  
63 #6 Str. 600 MCM 5/8 - 18 NF2
88  #6 Str.  1000 MCM     7/8 - 14 NF2
112   1250 MCM 2000 MCM 1-1/8 - 12 NF2


Outlet sizes larger than #63 may be used to advantage in meeting higher load conditions for present installations or for the planning of higher loads on future installations. The following Table 2. shows the available outlet sizes and their positions for the various ampere capacity MICONS.

TABLE 2.

MICON Current Rating Amperes

Positions A and/ or R

Positions All Remaining

1500 #63 or    #88 #63
2000 #63 or    #88, or #112 #63 or    #88
2500 #63 or    #88, or #112 #63 or    #88, or #112
3000 #63 or    #88, or #112 #63 or    #88, or #112

For making proper selection of a MICON connector requiring a cable outlet connection larger than 600 MCM the following steps should be followed:


ELECTRICAL
CONNECTORS

(A.)    Choose the desired catalog number from the MICONS shown on pages UG-16 to UG-19.

(B.)    Using Table 1. select the outlet size number required for the size cable employed.

(C.)    Using Table 2. determine the available outlet positions for cables larger than 600 MCM.

(D.)    Specify your MICON connector by the following order example:

Assume that an 8 outlet MICON connector in type MCI for 2000 ampere current rating is required. This would call for catalog number MCD 200-8. Let it further be assumed that cable sizes will be required for outlets in accordance with the following schedule:

Outlet Position

Cable Size

A 1500 MCM
B 750 MCM
C 800 MCM
R 750 MCM

ORDER FOR TYPE MCD SHOULD BE WRITTEN:

 

Outlet Positions

Outlet Size

MCD 200-8 A #112
  B,C,R #88
  Remaining Outlets #63

The wide overlapping of conductor sizes for outlet sizes # and #88 permits one to use a #88 outlet with any cable size within the range of the #63 outlet. As future load requirements necessitate

larger cables one can connect to the #88 outlet cable sizes from our 600 MCM to 1000 MCM inclusive. Where no future expansion of load requirements is anticipated it is most economical to select the Y63 outlet.

For all MICONS and insulating accessories MYPAR insulation is used as standard procedure. To specify MYPRENE insulation add the suffix "-N" to the catalog number of any part for which MYPRENE insulation is desired.