ALUMINUM
BUS PHYSICAL ELECTRICAL CHARACTERISTICS - STANDARD PIPE SIZES
Standard Iron Pipe Size, Inches
Diameter, Inches
Wall Thickness, Inches
Area, SQ. IN.
Weight. LB. Per FT.
Resistance Microhms Per FT.
Moment of Inertia. IN.4
Section Modules IN.³
Radius of Gyration, Inches
Current Capacity, Amperes, 60-Cycle
A.C.
Outside
Inside
¼
0.540
0.364
0.088
0.125
0.147
106.82
0.0033
0.0123
0.1628
200
3/8
0.675
0.493
0.091
0.167
0.196
80.42
0.0073
0.0216
0.2090
250
½
0.840
0.622
0.109
0.250
0.294
53.44
0.0171
0.0407
0.2613
340
¾
1.050
0.824
0.113
0.333
0.390
40.10
0.0370
0.0705
0.3337
435
1
1.315
1.049
0.133
0.494
0.580
26.97
0.0873
0.1328
0.4205
590
1¼
1.660
1.380
0.140
0.668
0.785
19.99
0.1947
0.2346
0.5397
740
1½
1.900
1.610
0.145
0.800
0.939
16.70
0.3099
0.3262
0.6226
840
2
2.375
2.067
0.154
1.075
1.262
12.42
0.6657
0.5606
0.7871
1100
2½
2.875
2.469
0.203
1.704
2.002
7.82
1.5300
1.0649
0.9474
1490
3
3.500
3.068
0.216
2.228
2.617
5.98
3.0177
1.7244
1.1640
1765
3½
4.000
3.548
0.226
2.680
3.147
4.78
4.7877
2.3938
1.3370
2030
4
4.500
4.026
0.237
3.174
3.729
4.21
7.2325
3.2144
1.5100
2300
4½
5.000
4.506
0.247
3.688
4.333
3.62
10.4433
4.1773
1.6830
2730
5
5.563
5.047
0.258
4.300
5.051
3.11
15.1600
5.4510
1.8780
3100
6
6.625
6.065
0.280
5.581
6.556
2.39
28.1400
8.4960
2.2450
3860
NOTES:
For outdoor locations with a cross wind of 2 feet per second, the ratings for tubes 1
inch and above may be increased 14 to 22 per cent, depending upon conductor
diameter. The increase for smaller conductors is somewhat higher.
Current ratings are for 30° C. rise over 40° C. ambient temperature in still but
unconfined air.