Technical Information
Technical Information
Dossert Home Page

MULTIPLYING FACTORS FOR CONVERTING D.C.
RESISTANCE TO 60 CYCLE A.C. RESISTANCE

Size

Multiplying Factor

For Nonmetallic Sheathed Cables in Air or Nonmetallic Conduit

For Metallic Sheathed Cables or all Cables in Metallic Raceways

Copper

Aluminum

Copper

Aluminum

Up to 3 AWG
          2
          1

1.
1.
1.

1.
1.
1.
1.
1.01
1.01
1.
1.00
1.00

0
00
000
0000

1.001
1.001
1.002
1.004
1.000
1.001
1.001
1.002
1.02
1.03
1.04
1.05
1.00
1.00
1.01
1.01
250000 CM
300000 CM
350000 CM
400000 CM

1.005
1.006
1.009
1.011

1.002
1.003
1.004
1.005
1.06
1.07
1.08
1.10
1.02
1.02
1.03
1.04
500000 CM
600000 CM
700000 CM
750000 CM
1.018
1.025
1.034
1.039
1.007
1.010
1.013
1.015
1.13
1.16
1.19
1.21
1.06
1.08
1.11
1.12
800000 CM
1000000 CM
1250000 CM
1500000 CM
1.044
1.067
1.102
1.142
1.017
1.026
1.040
1.058
1.22
1.30
1.41
1.53
1.14
1.19
1.27
1.36
1750000 CM
2000000 CM
1.185
1.233
1.079
1.100
1.67
1.82
1.46
1.56

The resistance values given are applicable only to direct current. When conductors larger than 4/0 are used with alternating current, the above multiplying factors must be used.